Fire door regulations

Fire door regulations explained

Every building with a fire door has someone legally responsible for keeping it working. Here are the laws and standards that apply, what each one asks of you, and where they differ across the UK.

In short: the Responsible Person must keep fire doors maintained and in good repair under the Fire Safety Order. In England, residential blocks over 11 metres must also check communal fire doors every three months and flat entrance doors every year under Regulation 10.

Correct as of October 2026. General information, not legal advice.

The laws

England and Wales

Regulatory Reform (Fire Safety) Order 2005

The Responsible Person must carry out a fire risk assessment and keep fire safety measures, including fire doors, maintained and in good repair. Applies to almost every non-domestic building and the common parts of residential blocks.

England and Wales

Fire Safety Act 2021

Confirmed the Fire Safety Order covers a block's structure, external walls and flat entrance doors opening onto common parts.

England only

Fire Safety (England) Regulations 2022, Regulation 10

Since 23 January 2023: in residential buildings over 11 metres, quarterly checks of communal fire doors and "best endeavours" annual checks of flat entrance doors. All multi-occupied residential buildings must give residents fire door information.

England

Building Safety Act 2022

Higher-risk buildings (18 metres or more, or 7+ storeys) need an Accountable Person, a safety case and a "golden thread" of digital building information, which fire door records feed into.

Worth knowing: the law does not require a specialist for routine Regulation 10 checks. Home Office guidance says Responsible Persons should be able to do them with simple instruction. A full inspection against each door's test evidence is different, and needs a competent inspector.

Standards and guidance

DocumentWhat it covers
BS 8214:2026Code of practice for fire and smoke control doors. Published 20 March 2026, replacing the timber-only 2016 edition. Now covers timber, steel, aluminium and composite doors.
BS 9999 and BS 9991Fire safety in the design, management and use of buildings (BS 9991 for residential).
Approved Document BBuilding Regulations guidance on fire safety, including where fire doors are needed.
The door's own test evidenceEach door's test and certification evidence. It always overrides general rules of thumb.

Building Regulations and fire doors

The Building Regulations decide where fire doors go in the first place. The Fire Safety Order then decides how they're looked after once the building is in use.

  • When they apply. In England, the Building Regulations 2010 apply when a building is built, extended, converted or materially altered. Part B covers fire safety.
  • Approved Document B is the official guidance on meeting Part B. It sets out where fire doors are needed and the fire resistance they need, for example on flat entrance doors, protected stairways and corridors, and plant or store rooms.
  • Houses. Fire doors are usually only needed in a house where there's a floor more than 4.5 metres above ground, such as after a loft conversion.
  • At handover. On new and altered buildings, Regulation 38 requires fire safety information, including about fire doors, to be passed to the Responsible Person.
  • Elsewhere in the UK. Wales has its own Approved Document B. Scotland and Northern Ireland have separate building standards.

Fitting and replacing fire doors: see fire door installation and regulations.

Across the UK

  • England: Fire Safety Order, Fire Safety Act, Regulation 10 and the Building Safety Act.
  • Wales: Fire Safety Order and Fire Safety Act apply, but Regulation 10's check schedule does not.
  • Scotland and Northern Ireland: separate fire safety laws apply. Check the local position.

Enforcement

Fire and rescue services enforce the Fire Safety Order. They can issue notices and prosecute, and fines can be unlimited. The Building Safety Regulator, independent of the HSE since 27 January 2026, oversees higher-risk buildings.

Key dates

  1. 2006Fire Safety Order in force
  2. June 2017Grenfell Tower fire
  3. April 2022Building Safety Act becomes law
  4. May 2022Fire Safety Act commenced
  5. January 2023Regulation 10 fire door checks in force
  6. January 2026Building Safety Regulator becomes independent of the HSE
  7. March 2026BS 8214:2026 published; FDIS gains UKAS accreditation for certifying inspectors
  8. April 2026Residential evacuation plan regulations in force

Questions we get asked

How often should fire doors be inspected?

In England, residential buildings over 11 metres must have communal fire doors checked every three months and flat entrance doors checked at least once a year on a “best endeavours” basis, under Regulation 10 of the Fire Safety (England) Regulations 2022 (in force since 23 January 2023).

For other buildings, the frequency should be set by your fire risk assessment. Many buildings use a professional inspection every six months with routine visual checks in between. Busy or high-traffic doors may need checking more often.

Last reviewed October 2026

Who is responsible for fire doors in a block of flats?

The Responsible Person under the Regulatory Reform (Fire Safety) Order 2005, usually the freeholder, a residents’ management company or right-to-manage company, often acting through a managing agent. They must keep fire doors maintained and in good repair.

The Fire Safety Act 2021 confirmed that this duty covers flat entrance doors opening onto common parts, as well as communal doors. Who owns and pays for an individual flat door depends on the lease.

Last reviewed October 2026

Who can inspect fire doors?

The law does not require a specialist for routine Regulation 10 checks: Home Office guidance says Responsible Persons should be able to carry them out with simple instruction. A full inspection is different. It needs someone competent to judge gaps, seals, hardware and alterations against the door’s test evidence and BS 8214:2026.

Recognised qualifications include FireQual qualifications, the ABBE Level 3 Award in Fire Door Inspection and Fire Door Inspection Scheme (FDIS) certification. Burnham’s inspections are carried out by FireQual-qualified inspectors.

Last reviewed October 2026

Can a fire door be held open?

Only with a suitable hold-open device that releases the door automatically when the fire alarm sounds. Wedges, fire extinguishers and door stops are never acceptable.

Hold-open devices need to be included in your fire risk assessment and tested along with the alarm.

Last reviewed October 2026

Are fire doors a legal requirement?

Where a building’s fire strategy or the Building Regulations call for fire doors, yes. Once they’re there, the Regulatory Reform (Fire Safety) Order 2005 requires the Responsible Person to keep them maintained and in good repair. Not every door in a building needs to be a fire door.

Last reviewed October 2026

What happens if fire doors aren't maintained?

Fire and rescue services enforce the Fire Safety Order. They can issue enforcement notices and prosecute, and fines can be unlimited. Poorly maintained doors can also cause problems with insurers and, most importantly, may not protect people in a fire.

Last reviewed October 2026

All fire door FAQs →

Book a survey or check where you stand.

Call or email and we'll talk through your doors, arrange a survey and send you a quote. Or take the free Compliance Check first.

Check your compliance